Catalogue of air attenuation
Each catalogue has a page of its own: choose another one here and open it, or narrow the rows of this one by name and by the table that printed them.
The six conditions the building standard’s own room model tabulates the air attenuation for, and the coefficient in each of them, band by band. A room model needs one. The air in a hall absorbs, the absorption grows with frequency and with dryness, and by 8 kHz it is no longer a correction to the surfaces but a term that decides the answer, which is why the model has an air term at all. So the standard prints a short table of two temperatures crossed with three ranges of relative humidity, and names the one to assume when the room’s own temperature and humidity are not known. That row carries a note here saying so.
The coefficient is a power attenuation in neper per metre, which is what the standard’s own air term takes, and it is not the decibel per metre an outdoor propagation model works in. The page prints it in thousandths of a neper per metre and so does this table. Six rows is all there is: this is a table to look a value up in and not a model to interpolate, and the standard says nothing about a room at 15 °C and 60 % that would let a row be made for it.
Italic is a value this library worked out; a dotted underline is a cell that is not a plain number, and what it is reads on the cell; an asterisk is a note the page made about the row. Click a mark to read it, or give the table focus and press Enter to walk the marks with the arrow keys.
| Condition | 125 Hz mNp/m | 250 Hz mNp/m | 500 Hz mNp/m | 1 kHz mNp/m | 2 kHz mNp/m | 4 kHz mNp/m | 8 kHz mNp/m | Source |
|---|---|---|---|---|---|---|---|---|
| 10 °C, 30-50 % | 0.1 | 0.2 | 0.5 | 1.1 | 2.7 | 9.4 | 29 | EN 12354-6:2003 Table 1 |
| 10 °C, 50-70 % | 0.1 | 0.2 | 0.5 | 0.8 | 1.8 | 5.9 | 21.1 | EN 12354-6:2003 Table 1 |
| 10 °C, 70-90 % | 0.1 | 0.2 | 0.5 | 0.7 | 1.4 | 4.4 | 15.8 | EN 12354-6:2003 Table 1 |
| 20 °C, 30-50 % | 0.1 | 0.3 | 0.6 | 1 | 1.9 | 5.8 | 20.3 | EN 12354-6:2003 Table 1 |
| 20 °C, 50-70 % The condition clause 4.3 recommends when the room's own temperature and humidity are not known. | 0.1 | 0.3 | 0.6 | 1 | 1.7 | 4.1 | 13.5 | EN 12354-6:2003 Table 1 |
| 20 °C, 70-90 % | 0.1 | 0.3 | 0.6 | 1.1 | 1.7 | 3.5 | 10.6 | EN 12354-6:2003 Table 1 |
References
Section titled “References”- European Committee for Standardization. (2003). Building acoustics — Estimation of acoustic performance of buildings from the performance of elements — Part 6: Sound absorption in enclosed spaces (EN 12354-6:2003). Table 1: the source of the rows of the catalogue of air attenuation that cite it.