# Errata in ISO 10140

> One page of the phonometry documentation, as Markdown. Index: https://docs.jmrp.io/phonometry/llms.txt

Canonical: https://docs.jmrp.io/phonometry/reference/errata/iso-10140/
Language: en
Alternate: https://docs.jmrp.io/phonometry/es/reference/errata/iso-10140/index.md
Version: phonometry 4.0.0
Install: pip install "phonometry[full]"
Author: José Manuel Requena Plens (https://orcid.org/0000-0003-1250-6212)
Published: 2026-10-28
Updated: 2026-10-28T03:12:25Z
License: MIT (https://github.com/jmrplens/phonometry/blob/main/LICENSE)
Summary: Errata in ISO 10140: 3 defects in the printed text, with the evidence and what phonometry does about each.

---

These are the 3 entries of the [errata registry](https://docs.jmrp.io/phonometry/reference/errata/) on ISO 10140-1:2021, in the order the registry lists them. The registry's introduction says how each claim is checked against the printed page and what the status of an entry means.

## ISO 10140-1:2021, Annex H, Figure H.4 (a CI,r,50-2500 the reference floor cannot give)

- **Location:** Annex H, Figure H.4 "Example of form for expression of
  results" (printed p. 31), the rating line under the diagram. The form of
  ISO 10140-1:2010+A2:2014, Figure H.4 (printed p. 27), carries the same term.
- **The print:** "Rating in accordance with ISO 717-2: $\Delta L_w$ = dB;
  $C_{I\Delta}$ = dB; $C_{I,r,50\text{–}2\,500}$ = dB". The 2010 form prints
  "$C_{I,r}$ = dB; $C_{I,r,50\text{-}2\,500}$ = dB" in the same line.
- **The problem:** $C_{I,r}$ is the spectrum adaptation term of the reference
  floor with the covering (ISO 717-2:2020 A.2.2), taken from
  $L_{n,r} = L_{n,r,0} - \Delta L$ (Formula (1)). ISO 717-2:2020 Table 4
  defines $L_{n,r,0}$ only from 100 Hz to 3 150 Hz, and the enlarged range of
  the NOTE to A.2.1 needs 50, 63 and 80 Hz as well, so no $L_{n,r}$ exists in
  those three bands and neither document defines $C_{I,r,50\text{–}2\,500}$.
  The form's own table asks for $\Delta L$ from 50 Hz, the three bands where
  the reference values would be needed. H.5 i), which the form illustrates,
  asks for $L_{n,r,w}$ and $C_{I,r}$ or $L_{n,0,w}$ and $C_{I,0}$, all of
  which Table 4 can give.
- **Evidence:** the rating line of the form against ISO 717-2:2020 A.2.1, A.2.2
  and Table 4, and against H.5 h) and i) of the same annex. Verified on PDF
  pages 35 and 37 (printed pp. 29 and 31) of ISO 10140-1:2021, on PDF pages 13,
  17 and 18 (printed pp. 7, 11 and 12) of ISO 717-2:2020, and on PDF page 36
  (printed p. 27) of BS EN ISO 10140-1:2010+A2:2014.
- **Library behaviour:** `building.laboratory_floor_covering_improvement` reports the
  two ratings H.5 i) asks for and no $C_{I,r,50\text{–}2\,500}$; the
  enlarged-range term of the measured bare floor, which is defined, comes from
  `building.weighted_impact_rating_extended`. The form itself is printed by
  `LaboratoryFloorCoveringImprovementResult.report()`, which puts those two ratings
  beside $\Delta L_w$ and $C_{I\Delta}$ and writes, where
  $C_{I,r,50\text{–}2\,500}$ would go, that it is not formed because Table 4
  starts at 100 Hz. No number the library reports depends on the form, and no
  change was required.
- **Status:** unreported.

## ISO 10140-1:2021, Annex J, Figure J.7 ("weighing curve" for "weighting curve")

- **Location:** Annex J, J.5.1, Figure J.7 "Sample form for expression of
  results" (PDF page 50, printed p. 44), the key beside the last two rows of
  the header of the form.
- **The print:** "................ frequency range of weighing curve" above
  "__________ test curve".
- **The problem:** "weighing" for "weighting". The dotted line marks the
  frequency range of the reference curve that the ISO 717-1 rating shifts, the
  weighting curve; a weighing curve is a term of neither document. The form of
  BS EN ISO 10140-1:2010+A2:2014, Figure J.7, prints "frequency range of
  weighting curve" in the same place, so the letter was lost in the 2021
  edition.
- **Evidence:** Verified on PDF page 50 (printed p. 44) of ISO 10140-1:2021
  against PDF page 49 (printed p. 40) of BS EN ISO 10140-1:2010+A2:2014.
- **Library behaviour:** none to take; no number depends on it. The form that
  `LaboratoryJointInsulationResult.report()` prints labels the curve "shifted
  reference (ISO 717-1)" and draws it over the rating range only.
- **Status:** unreported (typographic, no numerical consequence).

## ISO 10140-1:2021, Annex J, Figure J.8 (the working range drawn as Δb and keyed as Δbn)

- **Location:** Annex J, J.5.1, Figure J.8 (PDF page 52, printed p. 46), the
  dimension under the abscissa and the last line of the key. Figure J.8 of
  BS EN ISO 10140-1:2010+A2:2014 (PDF page 50, printed p. 41) prints the same
  pair.
- **The print:** the arrow between $b_\mathrm{n}$ and $b_\mathrm{n} + 3$ is
  labelled "$\Delta b$"; the key reads "$\Delta b_\mathrm{n}$ working range,
  3 mm".
- **The problem:** one quantity under two symbols, and the symbol the key
  explains is not the one drawn. The text that introduces the figure names it
  only in words, "indicating the working range of 3 mm" (J.5.1, PDF page 51,
  printed p. 45), so nothing else in the annex decides between the two.
- **Evidence:** Verified on PDF page 52 (printed p. 46) of ISO 10140-1:2021,
  the drawing against its key, with the text of J.5.1 on PDF page 51 (printed
  p. 45); and on PDF page 50 (printed p. 41) of BS EN ISO 10140-1:2010+A2:2014.
- **Library behaviour:** `JointGapSeries.working_range_mm` returns the two
  ends, $(b_\mathrm{n}, b_\mathrm{n} + 3)$, and its plot labels the shaded
  range "working range $\Delta b$ = 3 mm", the symbol of the drawing. No number
  depends on the symbol, and no change was required.
- **Status:** unreported (typographic, no numerical consequence).