# Catalogue of duct walls

> One page of the phonometry documentation, as Markdown. Index: https://docs.jmrp.io/phonometry/llms.txt

Canonical: https://docs.jmrp.io/phonometry/reference/catalogues/duct-walls/
Language: en
Alternate: https://docs.jmrp.io/phonometry/es/reference/catalogues/duct-walls/index.md
Version: phonometry 4.0.0
Install: pip install "phonometry[full]"
Author: José Manuel Requena Plens (https://orcid.org/0000-0003-1250-6212)
Published: 2026-10-28
Updated: 2026-11-16T21:36:14Z
Verified: 1 conformance checks (ASHRAE handbook: HVAC applications (SI edition)) https://docs.jmrp.io/phonometry/reference/conformance/#industrial-noise-control
Summary: Forty-six measurements of the sound that leaves a sheet metal duct through its wall and the sound that enters it, by size, shape, gauge and lining.

---

Forty-six measurements of what the wall of a sheet metal duct does to the sound
that crosses it, and the first thing to read on a row is which way it crossed.
Breakout is the sound that leaves the duct through its wall, into the room the
duct passes through. Break-in is the sound that enters the duct through the
same wall and then travels along it to somewhere else. They are two different
measurements of one wall and not two words for one number: the 305 mm by 305 mm
duct in 24 gauge is 21 dB at 63 Hz on the way out and 16 dB on the way in, and
27 against 16 at 250 Hz. Two rows that differ only in direction are two rows
here, and the column says which.

The rest of the row is what tells one duct from another. The shape is the
chapter's own word, which is why the breakout table says round where the
break-in table says circular for the same geometry. The gauge is the US sheet
metal gauge as printed, keeping the asterisk that marks a duct lined
internally, and the note on those rows says what the lining is. The size is the
two sides or the diameter, in millimetres; two rows carry a diameter the page
prints once over three consecutive rows, so those two are marked as worked out
rather than read. Several cells are a lower bound and not a value, because the
sound radiated was below the background in the room the duct was measured in,
and a bound is published as one.

Each value is the number its page prints, unless a word in brackets after it says what else it is:

- **carried**: the page gives this value on another of its rows
- **bound**: the page prints a bound and no value
- **unquantified**: the page prints a word here

A note mark after a name or a value points to the note the page makes about that row or cell, listed under the table.

| Duct | Direction | Shape | Sheet gauge | Diameter (mm) | First side (mm) | Second side (mm) | Duct length (m) | 63 Hz (dB) | 125 Hz (dB) | 250 Hz (dB) | 500 Hz (dB) | 1 kHz (dB) | 2 kHz (dB) | 4 kHz (dB) | 8 kHz (dB) | Source |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| 305 × 305 mm | breakout | rectangular | 24 |  | 305 | 305 |  | 21 | 24 | 27 | 30 | 33 | 36 | 41 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 305 × 610 mm | breakout | rectangular | 24 |  | 305 | 610 |  | 19 | 22 | 25 | 28 | 31 | 35 | 41 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 305 × 1220 mm | breakout | rectangular | 22 |  | 305 | 1 220 |  | 19 | 22 | 25 | 28 | 31 | 37 | 43 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 610 × 610 mm | breakout | rectangular | 22 |  | 610 | 610 |  | 20 | 23 | 26 | 29 | 32 | 37 | 43 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 610 × 1220 mm | breakout | rectangular | 20 |  | 610 | 1 220 |  | 20 | 23 | 26 | 29 | 31 | 39 | 45 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 1220 × 1220 mm | breakout | rectangular | 18 |  | 1 220 | 1 220 |  | 21 | 24 | 27 | 30 | 35 | 41 | 45 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 1220 × 2440 mm | breakout | rectangular | 18 |  | 1 220 | 2 440 |  | 19 | 22 | 25 | 29 | 35 | 41 | 45 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Long Seam Ducts: 200 mm[^ductTransmissionLoss-1] | breakout | round | 26 | 200 |  |  | 4.6 | > 45 (bound)[^ductTransmissionLoss-2] | 53 | 55 | 52 | 44 | 35 | 34 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Long Seam Ducts: 350 mm[^ductTransmissionLoss-3] | breakout | round | 24 | 350 |  |  | 4.6 | > 50 (bound)[^ductTransmissionLoss-4] | 60 | 54 | 36 | 34 | 31 | 25 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Long Seam Ducts: 560 mm[^ductTransmissionLoss-5] | breakout | round | 22 | 560 |  |  | 4.6 | > 47 (bound)[^ductTransmissionLoss-6] | 53 | 37 | 33 | 33 | 27 | 25 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Long Seam Ducts: 810 mm[^ductTransmissionLoss-7] | breakout | round | 22 | 810 |  |  | 4.6 | 51 | 46 | 26 | 26 | 24 | 22 | 38 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 300 mm[^ductTransmissionLoss-8] | breakout | round | 26\* | 300 |  |  | 3.6 | 52 | 51 | 53 | 51 | 50 | 46 | 36 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 610 mm | breakout | round | 24 | 610 |  |  | 7.3 | 51 | 53 | 51 | 44 | 36 | 26 | 29 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 610 mm[^ductTransmissionLoss-9] | breakout | round | 24\* | 610 (carried)[^ductTransmissionLoss-10] |  |  | 7.3 | 51 | 51 | 54 | 44 | 39 | 33 | 47 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 610 mm[^ductTransmissionLoss-11] | breakout | round | 16 | 610 (carried)[^ductTransmissionLoss-12] |  |  | 3 | > 48 (bound)[^ductTransmissionLoss-13] | 53 | 36 | 32 | 32 | 28 | 41 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 915 mm | breakout | round | 20 | 915 |  |  | 7.3 | 51 | 51 | 52 | 46 | 36 | 32 | 55 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 305 × 152 mm | breakout | flat oval | 24 |  | 305 | 152 |  | 31 | 34 | 37 | 40 | 43 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 610 × 152 mm | breakout | flat oval | 24 |  | 610 | 152 |  | 24 | 27 | 30 | 33 | 36 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 610 × 305 mm | breakout | flat oval | 24 |  | 610 | 305 |  | 28 | 31 | 34 | 37 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 1220 × 305 mm | breakout | flat oval | 22 |  | 1 220 | 305 |  | 23 | 26 | 29 | 32 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 1220 × 610 mm | breakout | flat oval | 22 |  | 1 220 | 610 |  | 27 | 30 | 33 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 2440 × 610 mm | breakout | flat oval | 20 |  | 2 440 | 610 |  | 22 | 25 | 28 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 2440 × 1220 mm | breakout | flat oval | 18 |  | 2 440 | 1 220 |  | 28 | 31 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Long Seam Ducts: 203 mm[^ductTransmissionLoss-15] | break-in | circular | 26 | 203 |  |  | 4.57 | > 17 (bound)[^ductTransmissionLoss-16] | 31 | 39 | 42 | 41 | 32 | 31 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Long Seam Ducts: 356 mm[^ductTransmissionLoss-17] | break-in | circular | 24 | 356 |  |  | 4.57 | > 27 (bound)[^ductTransmissionLoss-18] | 43 | 43 | 31 | 31 | 28 | 22 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Long Seam Ducts: 559 mm[^ductTransmissionLoss-19] | break-in | circular | 22 | 559 |  |  | 4.57 | > 28 (bound)[^ductTransmissionLoss-20] | 40 | 30 | 30 | 30 | 24 | 22 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Long Seam Ducts: 813 mm[^ductTransmissionLoss-21] | break-in | circular | 22 | 813 |  |  | 4.57 | 35 | 36 | 23 | 23 | 21 | 19 | 35 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 203 mm[^ductTransmissionLoss-22] | break-in | circular | 26 | 203 |  |  | 3.05 | > 20 (bound)[^ductTransmissionLoss-23] | > 42 (bound)[^ductTransmissionLoss-24] | > 59 (bound)[^ductTransmissionLoss-25] | > 62 (bound)[^ductTransmissionLoss-26] | 53 | 43 | 26 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 356 mm[^ductTransmissionLoss-27] | break-in | circular | 26 | 356 |  |  | 3.05 | > 20 (bound)[^ductTransmissionLoss-23] | > 36 (bound)[^ductTransmissionLoss-28] | 44 | 28 | 31 | 32 | 22 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 660 mm[^ductTransmissionLoss-17] | break-in | circular | 24 | 660 |  |  | 3.05 | > 27 (bound)[^ductTransmissionLoss-18] | 38 | 20 | 23 | 22 | 19 | 33 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 660 mm[^ductTransmissionLoss-29] | break-in | circular | 16 | 660 |  |  | 3.05 | > 30 (bound)[^ductTransmissionLoss-30] | > 41 (bound)[^ductTransmissionLoss-31] | 30 | 29 | 29 | 25 | 38 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| Spiral Wound Ducts: 813 mm[^ductTransmissionLoss-17] | break-in | circular | 22 | 813 |  |  | 3.05 | > 27 (bound)[^ductTransmissionLoss-18] | 32 | 25 | 22 | 23 | 21 | 37 |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 305 × 305 mm | break-in | rectangular | 24 |  | 305 | 305 |  | 16 | 16 | 16 | 25 | 30 | 33 | 38 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 305 × 610 mm | break-in | rectangular | 24 |  | 305 | 610 |  | 15 | 15 | 17 | 25 | 28 | 32 | 38 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 305 × 1220 mm | break-in | rectangular | 22 |  | 305 | 1 220 |  | 14 | 14 | 22 | 25 | 28 | 34 | 40 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 610 × 610 mm | break-in | rectangular | 22 |  | 610 | 610 |  | 13 | 13 | 21 | 26 | 29 | 34 | 40 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 610 × 1220 mm | break-in | rectangular | 20 |  | 610 | 1 220 |  | 12 | 15 | 23 | 26 | 28 | 36 | 42 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 1220 × 1220 mm | break-in | rectangular | 18 |  | 1 220 | 1 220 |  | 10 | 19 | 24 | 27 | 32 | 38 | 42 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 1220 × 2440 mm | break-in | rectangular | 18 |  | 1 220 | 2 440 |  | 11 | 19 | 22 | 26 | 32 | 38 | 42 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 305 × 152 mm[^ductTransmissionLoss-32] | break-in | flat oval | 24 |  | 305 | 152 |  | 18 | 18 | 22 | 31 | 40 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 610 × 152 mm[^ductTransmissionLoss-32] | break-in | flat oval | 24 |  | 610 | 152 |  | 17 | 17 | 18 | 30 | 33 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 610 × 305 mm[^ductTransmissionLoss-32] | break-in | flat oval | 24 |  | 610 | 305 |  | 15 | 16 | 25 | 34 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 1220 × 305 mm[^ductTransmissionLoss-32] | break-in | flat oval | 22 |  | 1 220 | 305 |  | 14 | 14 | 26 | 29 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 1220 × 610 mm[^ductTransmissionLoss-32] | break-in | flat oval | 22 |  | 1 220 | 610 |  | 12 | 21 | 30 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 2440 × 610 mm[^ductTransmissionLoss-32] | break-in | flat oval | 20 |  | 2 440 | 610 |  | 11 | 22 | 25 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
| 2440 × 1220 mm[^ductTransmissionLoss-32] | break-in | flat oval | 18 |  | 2 440 | 1 220 |  | 19 | 28 | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] | — (unquantified)[^ductTransmissionLoss-14] |  | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |

[^ductTransmissionLoss-1]: The 63 Hz cell is printed “>45”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “(53)”. The only legend for that mark anywhere on folios 49.30 to 49.32 is the note under Table 32: “Parentheses indicate measurements in which background sound produced greater uncertainty than usual.” No hedge of this catalogue means that, and approximate is for a number an author rounded on purpose, so the number is held exactly as printed and the mark is recorded here.
[^ductTransmissionLoss-2]: the page prints a lower bound of 45 and no value
[^ductTransmissionLoss-3]: The 63 Hz cell is printed “>50”, a lower bound and not a value; the page gives no ceiling for it and none is invented.
[^ductTransmissionLoss-4]: the page prints a lower bound of 50 and no value
[^ductTransmissionLoss-5]: The 63 Hz cell is printed “>47”, a lower bound and not a value; the page gives no ceiling for it and none is invented.
[^ductTransmissionLoss-6]: the page prints a lower bound of 47 and no value
[^ductTransmissionLoss-7]: The 63 Hz cell is printed “(51)”. The only legend for that mark anywhere on folios 49.30 to 49.32 is the note under Table 32: “Parentheses indicate measurements in which background sound produced greater uncertainty than usual.” No hedge of this catalogue means that, and approximate is for a number an author rounded on purpose, so the number is held exactly as printed and the mark is recorded here.
[^ductTransmissionLoss-8]: The gauge carries the asterisk of the footnote printed under Table 30: “\*Ducts internally lined with 25 mm thick 24 kg/m3 fiberglass with 0.6 mm perforated sheet metal inner liner.” (the page sets the 3 of the density as a superscript).
[^ductTransmissionLoss-9]: The diameter cell is blank on the page, and the 610 mm this row serves is carried down from the row of its block that prints it rather than read from this row. The gauge carries the asterisk of the footnote printed under Table 30: “\*Ducts internally lined with 25 mm thick 24 kg/m3 fiberglass with 0.6 mm perforated sheet metal inner liner.” (the page sets the 3 of the density as a superscript).
[^ductTransmissionLoss-10]: carried down from the 610 mm printed one row above it. The page prints the diameter once for that part of the Spiral Wound Ducts block of Table 30 and leaves the cell blank on the two rows below it, which print their own length and gauge.
[^ductTransmissionLoss-11]: The diameter cell is blank on the page, and the 610 mm this row serves is carried down from the row of its block that prints it rather than read from this row. The length is printed as a bare “3”, with no decimal, where every other length in Tables 30 and 32 carries one. The 63 Hz cell is printed “>48”, a lower bound and not a value; the page gives no ceiling for it and none is invented.
[^ductTransmissionLoss-12]: carried down from the 610 mm printed two rows above it. The page prints the diameter once for that part of the Spiral Wound Ducts block of Table 30 and leaves the cell blank on the two rows below it, which print their own length and gauge.
[^ductTransmissionLoss-13]: the page prints a lower bound of 48 and no value
[^ductTransmissionLoss-14]: the page prints “—” where the number would be
[^ductTransmissionLoss-15]: The 63 Hz cell is printed “>17”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “(31)”. The note printed under this table reads: “Parentheses indicate measurements in which background sound produced greater uncertainty than usual.” No hedge of this catalogue means that, and approximate is for a number an author rounded on purpose, so the number is held exactly as printed and the mark is recorded here.
[^ductTransmissionLoss-16]: the page prints a lower bound of 17 and no value
[^ductTransmissionLoss-17]: The 63 Hz cell is printed “>27”, a lower bound and not a value; the page gives no ceiling for it and none is invented.
[^ductTransmissionLoss-18]: the page prints a lower bound of 27 and no value
[^ductTransmissionLoss-19]: The 63 Hz cell is printed “>28”, a lower bound and not a value; the page gives no ceiling for it and none is invented.
[^ductTransmissionLoss-20]: the page prints a lower bound of 28 and no value
[^ductTransmissionLoss-21]: The 63 Hz cell is printed “(35)”. The note printed under this table reads: “Parentheses indicate measurements in which background sound produced greater uncertainty than usual.” No hedge of this catalogue means that, and approximate is for a number an author rounded on purpose, so the number is held exactly as printed and the mark is recorded here.
[^ductTransmissionLoss-22]: The 63 Hz cell is printed “>20”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “>42”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 250 Hz cell is printed “>59”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 500 Hz cell is printed “>62”, a lower bound and not a value; the page gives no ceiling for it and none is invented.
[^ductTransmissionLoss-23]: the page prints a lower bound of 20 and no value
[^ductTransmissionLoss-24]: the page prints a lower bound of 42 and no value
[^ductTransmissionLoss-25]: the page prints a lower bound of 59 and no value
[^ductTransmissionLoss-26]: the page prints a lower bound of 62 and no value
[^ductTransmissionLoss-27]: The 63 Hz cell is printed “>20”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “>36”, a lower bound and not a value; the page gives no ceiling for it and none is invented.
[^ductTransmissionLoss-28]: the page prints a lower bound of 36 and no value
[^ductTransmissionLoss-29]: The 63 Hz cell is printed “>30”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “>41”, a lower bound and not a value; the page gives no ceiling for it and none is invented.
[^ductTransmissionLoss-30]: the page prints a lower bound of 30 and no value
[^ductTransmissionLoss-31]: the page prints a lower bound of 41 and no value
[^ductTransmissionLoss-32]: Table 34 is printed twice, complete, on folio 49.31 and again on folio 49.32. The two printings were compared row by row and agree, marks included, so one set of rows is kept.

## References

- **American Society of Heating, Refrigerating and Air-Conditioning Engineers. (2019).** *ASHRAE handbook: HVAC applications (SI edition), Chapter 49, Noise and vibration control*. ASHRAE.
  Chapter 49, Tables 29 to 34: the source of the rows of the catalogue of duct walls that cite it.