# Linings, Floor Coverings, Joints and Rain (ISO 10140-1)

Most of ISO 10140 measures what an element *is*: the sound reduction index of
a wall, the impact level under a floor. Four of the application rules of
ISO 10140-1 measure something else. Annex G measures what a **lining** adds to
the wall it is fixed to, Annex H what a **floor covering** takes off the impact
level of the floor it is laid on, Annex J what a **joint** lets through, a
metre of it at a time, and Annex K what **rain** does to a roof, a roof window
or a rooflight. The first two are products that are never sold on their own,
so the laboratory measures the element twice, without and with the product,
and reports the difference. A joint is a line rather than an area, measured in
an element built to hide everything else. Rain is an impact source that falls
from the sky rather than from a tapping machine, so the laboratory has to make
its own rain.

The measurements themselves are the ones of
[Laboratory Insulation Measurement](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-lab/):
$R$ to ISO 10140-2 and $L_\mathrm{n}$ to ISO 10140-3, in a suite where flanking
is suppressed. What this page adds is what the annexes do with them, and the
single numbers that make two laboratories agree about a product whose effect
depends on what it is fixed to.

## Linings: the improvement ΔR (Annex G)

A lining is an additional layer on a wall or a ceiling: a plasterboard skin on
studs, an external thermal insulation system, a dry lining glued to masonry.
Annex G measures the basic element without and then with it and reports the
**sound reduction improvement index** in every one-third-octave band,

$$
\Delta R = R_\mathrm{with} - R_\mathrm{without}
$$

(G.1). The improvement is not a property of the lining alone. It is only
independent of the wall when the wall is much heavier than the lining, its
critical frequency lies below the measured range and the two are weakly
coupled (G.2); a lining on a lightweight wall behaves differently because the
wall's own coincidence moves the result. So G.2 names the walls to measure on:
the **standard basic elements** of ISO 10140-5:2021 Annex B.

| Basic element | Construction | $R_\mathrm{w}$ ($C$; $C_\mathrm{tr}$) of its reference curve |
| :--- | :--- | :--- |
| Heavy wall | masonry or concrete of (350 ± 50) kg/m², critical frequency in the 125 Hz octave | 53 (−1; −5) dB |
| Heavy floor | the reinforced concrete slab of the heavyweight reference floor | 52 (−1; −5) dB |
| Lightweight wall | 10 cm aerated concrete of (600 ± 50) kg/m³ plastered, about 70 kg/m², critical frequency in the 500 Hz octave | 33 (−1; −2) dB |

The laboratory's own wall is never exactly the reference one, so the single
number is not read off the two measured curves. ISO 717-1:2020 Annex D adds
the measured $\Delta R$ to the **reference curve** of the element,
$R_\mathrm{ref,with} = R_\mathrm{ref,without} + \Delta R$ (Formula (D.3)),
rates both curves, and takes the difference:
$\Delta R_\mathrm{w} = R_\mathrm{w,ref,with} - R_\mathrm{w,ref,without}$
(Formula (D.4)). $\Delta(R_\mathrm{w} + C)$ and
$\Delta(R_\mathrm{w} + C_\mathrm{tr})$ follow in the same way, and so does
every enlarged-range term of Annex B the measured bands reach. The result
carries the element as an index, $\Delta R_\mathrm{w,heavy}$ or
$\Delta R_\mathrm{w,light}$. The reference curves are Table E.1 of
ISO 717-1:2020, published by the library as
`building.LINING_REFERENCE_ELEMENTS`; ISO 10140-5 printed the same numbers as
its Table B.1 until its 2021 edition moved them there.

```python
import numpy as np
from phonometry import building

freqs = [50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800,
         1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000]
# The laboratory's heavy wall, and the same wall with plasterboard on
# free-standing studs over mineral wool.
r_without = np.array([36.1, 37.0, 38.2, 39.5, 40.3, 41.2, 40.6, 41.8, 43.9,
                      46.4, 48.9, 51.6, 54.2, 56.5, 58.7, 61.4, 63.3, 64.2,
                      64.8, 65.9, 66.4])
delta_r = np.array([-2.1, -5.4, -3.2, 1.5, 4.8, 7.9, 10.6, 12.9, 14.7, 16.2,
                    17.4, 18.3, 19.1, 19.6, 19.9, 19.5, 18.2, 16.4, 15.8,
                    17.1, 18.0])
res = building.lab_lining_improvement(r_without, r_without + delta_r, freqs,
                                      basic_element="heavy_wall")
rating = res.rating
print(rating.index, rating.delta_rw, rating.delta_rw_c, rating.delta_rw_ctr)
# heavy 12 11 10
print(rating.without_lining.rating, rating.with_lining.rating)   # 53 65
print(rating.delta_rw_c_50_3150, rating.delta_rw_ctr_50_3150)   # 9 3
```

The lining costs a few decibels at its mass-spring-mass resonance near 63 Hz
and gains up to 20 dB above it; the traffic-weighted term, which leans on the
low bands, gains least, and the enlarged-range $C_\mathrm{tr,50\text{–}3150}$
sees the resonance itself and keeps only 3 dB.

On a wall that is not one of the three standard elements
(`basic_element=None`), Annex D has no reference curve to generalise with, and
G.2 c) allows only the **direct difference** of the measured single numbers,
$\Delta R_\mathrm{w,direct} = R_\mathrm{w,with} - R_\mathrm{w,without}$
(Formula (D.2)). It describes the lining on that wall in that laboratory and
nowhere else. The result carries it in every case, since it needs only the
two measured curves:

```python
print(res.delta_rw_direct_db, res.delta_rw_c_direct_db, res.delta_rw_ctr_direct_db)
# 13 12 9
other = building.lab_lining_improvement(r_without, r_without + delta_r, freqs,
                                        basic_element=None)
print(other.rating, other.delta_rw_direct_db)                   # None 13
```

The octave values of G.1, where a report wants them, come from the three
thirds of each octave by ISO 717-1:2020 Formula (D.1),
$\Delta R_\mathrm{oct} = -10 \log_{10}[(1/3) \sum 10^{-\Delta R_j/10}]$, which
averages the transmission factors rather than the decibels, so the third that
improves least weighs most; `res.octave_bands()` returns them.

### The wall must not change between the two measurements (G.4)

$\Delta R$ is a difference of two measurements of the same wall, so the wall
has to be the same wall both times. G.4 puts numbers on it for masonry and
concrete: a curing period of at least **two weeks** before the first
measurement, or, if the laboratory cannot wait, a time lag between the two
measurements of at most **one third** of the curing time already elapsed. Its
own example: two measurements carried out within one day can start three days
after the end of construction.

```python
check = building.check_lining_curing(10.0, 2.0)      # days
print(check.passes, check.cured, check.lag_within_third)   # True False True
print(building.check_lining_curing(2.9, 1.0).passes)       # False
```

The product specification may set another curing period
(`required_curing_days=`). The verdict has no truth value of its own: read
`.passes`, and `.plot()` draws the admissible region with the measurement in
it.

<picture><source media="(prefers-color-scheme: dark)" srcset="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/lab_lining_improvement_dark.svg"><img src="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/lab_lining_improvement.svg" alt="Two panels for one lining measured on the heavy standard wall. Left: the sound reduction improvement index over 21 one-third-octave bands from 50 Hz to 5000 Hz, negative at 50 to 80 Hz with its lowest point near minus 5 dB at 63 Hz, rising through zero at 100 Hz to about 20 dB at 1250 Hz, dipping to 16 dB around 2500 to 3150 Hz and recovering to 18 dB at 5000 Hz; the title reads delta R w heavy equals 12 dB. Right: the reference curve of the heavy wall, flat at 40 dB from 100 to 200 Hz and rising to 65 dB, with Rw 53 dB, and the same curve raised by the measured improvement, with Rw 65 dB" width="100%"></picture>

*One plasterboard lining on the heavy wall. On the left the improvement the
laboratory measured, band by band; on the right the two curves Annex D rates:
the reference wall of Table E.1 and the same wall with the lining's
$\Delta R$ added. The 12 dB between their ratings is $\Delta R_\mathrm{w,heavy}$,
a number that does not depend on the laboratory's own wall.*

<details>
<summary>Show the code for this figure</summary>

```python
import matplotlib.pyplot as plt
import numpy as np
from phonometry import building

freqs = [50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800,
         1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000]
r_without = np.array([36.1, 37.0, 38.2, 39.5, 40.3, 41.2, 40.6, 41.8, 43.9,
                      46.4, 48.9, 51.6, 54.2, 56.5, 58.7, 61.4, 63.3, 64.2,
                      64.8, 65.9, 66.4])
delta_r = np.array([-2.1, -5.4, -3.2, 1.5, 4.8, 7.9, 10.6, 12.9, 14.7, 16.2,
                    17.4, 18.3, 19.1, 19.6, 19.9, 19.5, 18.2, 16.4, 15.8,
                    17.1, 18.0])
res = building.lab_lining_improvement(r_without, r_without + delta_r, freqs)

fig, (ax1, ax2) = plt.subplots(1, 2, figsize=(13, 5.6))
res.plot(ax=ax1)
res.rating.plot(ax=ax2)
plt.tight_layout()
plt.show()
```

</details>

## Floor coverings: the improvement ΔL (Annex H)

A floor covering (a carpet, a vinyl or rubber sheet, a floating screed, a
parquet on an underlay) is laid on a **reference floor** and the tapping
machine is run on it with and without the covering at the same positions. The
improvement of impact sound insulation is

$$
\Delta L = L_\mathrm{n0} - L_\mathrm{n}
$$

(Formula (H.1)) in each one-third-octave band, and the octave value comes from
the three thirds by
$\Delta L_\mathrm{oct} = -10 \log_{10}[(1/3) \sum 10^{-\Delta L_j/10}]$
(Formula (H.2)), a mean of $10^{-\Delta L_j/10}$ in which the third that
improves least weighs most. As long as the receiving room's absorption does not change
between the two measurements, the reduction of $L_\mathrm{i}$ is the reduction
of $L_\mathrm{n}$ (NOTE to H.1).

The reference floor matters more than it does for a lining, because a covering
works against the stiffness of what is under it. ISO 10140-5:2021 Annex C
builds one **heavyweight** floor, a reinforced concrete slab of 120 mm
(+40/−20 mm, preferably 140 mm), and three **lightweight** (timber) floors that
stand for the joist floors built around the world:

| Reference floor | Construction (ISO 10140-5:2021 C.2.1, C.3.3) | Reference curve | $L_\mathrm{n,w}$ ($C_\mathrm{I}$) |
| :--- | :--- | :--- | :--- |
| Heavyweight | concrete slab, 120 mm | $L_\mathrm{n,r,0}$ | 78 (−11) dB |
| Lightweight No 1 | 22 mm chipboard on 120 mm × 180 mm joists at 625 mm, mineral wool, battens, 12,5 mm plasterboard | $L_\mathrm{n,t,r,0}$ | 72 (0) dB |
| Lightweight No 2 | 20 mm OSB, plywood or chipboard on 42 mm × 225 mm joists at 610 mm, mineral wool, resilient channels, two layers of plasterboard | the same curve as No 1 | 72 (0) dB |
| Lightweight No 3 | two layers of 15 mm plywood on 45 mm × 60 mm joists at 300 mm over 120 mm × 240 mm beams at 1 m | $L_\mathrm{n,t,r,0}$ | 75 (−3) dB |

The curves are Table 4 of ISO 717-2:2020, published as
`building.IMPACT_REFERENCE_FLOORS`; the 2010 edition of ISO 10140-5 printed
them as its Table C.1. They are what the single number is read on, in the same
way as for a lining: $L_\mathrm{n,r} = L_\mathrm{n,r,0} - \Delta L$
(ISO 717-2:2020 Formula (1)) and
$\Delta L_\mathrm{w} = L_\mathrm{n,r,0,w} - L_\mathrm{n,r,w}$
(Formula (2)). On the heavyweight floor the result is $\Delta L_\mathrm{w}$
(Clause 5); on a lightweight floor it is $\Delta L_\mathrm{t,1,w}$,
$\Delta L_\mathrm{t,2,w}$ or $\Delta L_\mathrm{t,3,w}$ (Clause 6), each with
its adaptation term $C_{\mathrm{I}\Delta}$ or $C_{\mathrm{I}\Delta,\mathrm{t}}$
(Formulas (A.4) and (A.6)).

```python
freqs = [100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250,
         1600, 2000, 2500, 3150, 4000, 5000]
# A resilient vinyl on the timber reference floor No 3.
l_n0 = np.array([70.5, 73.4, 75.8, 77.2, 78.9, 78.1, 77.6, 78.3, 77.1, 75.4,
                 73.8, 71.2, 68.9, 65.7, 62.8, 59.6, 56.9, 53.8])
delta_l = np.array([0.4, 0.8, 1.5, 2.3, 3.4, 4.9, 6.8, 9.1, 11.6, 14.2, 16.9,
                    19.8, 22.4, 25.1, 27.3, 29.4, 30.8, 31.9])
cover = building.lab_floor_covering_improvement(l_n0, l_n0 - delta_l, freqs,
                                                reference_floor="lightweight_3")
print(cover.designation, cover.delta_lw_db, cover.ci_delta_db)   # ΔLt,3,w 8 -3
print(cover.reference_rating.rating, cover.bare_rating.rating)   # 67 75
```

The two ratings at the end are the ones H.5 i) asks the report to state beside
$\Delta L$: the reference floor with the covering, $L_\mathrm{n,t,r,w}$, and the
measured bare floor, $L_\mathrm{n,0,w}$. The same $\Delta L$ read on the
heavyweight curve would give $\Delta L_\mathrm{w} = 18$ dB, because the
concrete reference is loudest where the vinyl works best, at high frequency,
and the timber one is loudest where it barely works at all. That is why
ISO 717-2:2020 5.4 confines a $\Delta L_\mathrm{w}$ measured on concrete to
massive floors, and why a covering meant for timber floors is rated on a
timber floor.

The two library functions that rate a $\Delta L$ spectrum directly,
`weighted_impact_improvement` and `impact_improvement_adaptation_term`, take the
same `reference_floor=` and, with `one_decimal=True`, the form ISO 717-2 5.4
prescribes when an uncertainty is stated beside the number.

### Specimens, positions and loads

Annex H sorts coverings into three categories, and the category decides the
specimen and the number of tapping-machine positions (H.2.2 and H.4.6):

- **Category I**, flexible coverings laid loose or glued (plastics, rubber,
  cork, matting): at least three small specimens of at least 650 mm × 350 mm,
  one tapping-machine position on each, hammers at least 100 mm from the
  edges. The bare floor may be measured at the same positions or with the
  machine either side of each specimen, averaging the two arithmetically; on a
  timber floor the line of hammers runs at 45° to the joists with at least one
  hammer over a joist.
- **Category II**, rigid or composite coverings, and **category III**,
  stretched coverings wall to wall: the whole floor or at least 10 m² with the
  shorter side at least 2,3 m; at least four machine positions on the
  heavyweight floor and six, randomly placed, on a lightweight one. A
  category II covering may be loaded with 20 kg/m² to 25 kg/m².

The floor surface should be between 18 °C and 25 °C (H.4.5). None of these
conditions changes the arithmetic, and none is checked: they are what the
test report has to state.

### The rubber ball and the mock-up floor (H.6)

H.6.1 measures the same covering under the heavy/soft impact source, the
rubber ball of ISO 10140-5:2021 Annex F, and reports the reduction of its
maximum level, $\Delta L_\mathrm{r} = L_\mathrm{i,Fmax,0} - L_\mathrm{i,Fmax}$
(Formula (H.3)):

```python
ball = building.heavy_impact_improvement([79.2, 73.5, 66.1, 58.4],
                                         [78.6, 71.9, 62.3, 51.0],
                                         [63, 125, 250, 500])
print(ball.improvement_db)                    # [0.6 1.6 3.8 7.4]
```

For a laboratory that cannot build a timber floor, H.6.2 allows a wooden
mock-up on the concrete slab instead (ISO 10140-5:2021 Annex G): a 22 mm
particleboard on twenty feet, loaded with five weights of 20 kg to 25 kg and
tapped at six fixed positions. Annex H names no reference curve for it, so its
$\Delta L$ describes the covering on a similar board, and the rating it is given
here is the one of the `reference_floor` the caller chooses.

<picture><source media="(prefers-color-scheme: dark)" srcset="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/lab_floor_covering_improvement_dark.svg"><img src="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/lab_floor_covering_improvement.svg" alt="Two panels. Left: the reference curves of ISO 717-2 Table 4 over the 16 bands from 100 Hz to 3150 Hz: the heavyweight floor rising slowly from 67 to 72 dB, the lightweight floors No 1 and No 2 flat at 78 dB up to 315 Hz and falling to 51 dB, and the lightweight floor No 3 rising from 69 to 78 dB, flat to 630 Hz and falling to 60 dB. Right: the improvement of a resilient vinyl on the lightweight floor No 3 over 18 bands, under 1 dB at 100 Hz and rising steadily to 32 dB at 5000 Hz; the title reads delta L t 3 w equals 8 dB with C I delta t 3 of minus 3 dB" width="100%"></picture>

*Left, the four reference floors, three curves because No 1 and No 2 share one.
The concrete slab is loudest at high frequency; the joist floors are loudest
below 400 Hz. Right, a resilient vinyl measured on floor No 3: an improvement
that grows with frequency and is rated at only 8 dB on the timber curve,
where the same spectrum would be rated at 18 dB on the concrete one.*

<details>
<summary>Show the code for this figure</summary>

```python
import matplotlib.pyplot as plt
import numpy as np
from phonometry import building

freqs = [100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250,
         1600, 2000, 2500, 3150, 4000, 5000]
l_n0 = np.array([70.5, 73.4, 75.8, 77.2, 78.9, 78.1, 77.6, 78.3, 77.1, 75.4,
                 73.8, 71.2, 68.9, 65.7, 62.8, 59.6, 56.9, 53.8])
delta_l = np.array([0.4, 0.8, 1.5, 2.3, 3.4, 4.9, 6.8, 9.1, 11.6, 14.2, 16.9,
                    19.8, 22.4, 25.1, 27.3, 29.4, 30.8, 31.9])
cover = building.lab_floor_covering_improvement(l_n0, l_n0 - delta_l, freqs,
                                                reference_floor="lightweight_3")

fig, (ax1, ax2) = plt.subplots(1, 2, figsize=(13, 5.6))
floors = building.IMPACT_REFERENCE_FLOORS
x = np.arange(16)
for key, style in (("heavyweight", "s--"), ("lightweight_1", "o-"),
                   ("lightweight_3", "^-")):
    ax1.plot(x, list(floors[key].values()), style, label=key)
ax1.set_xticks(x, [f"{f:g}" for f in floors["heavyweight"]], rotation=45)
ax1.set(xlabel="Frequency [Hz]", ylabel="Impact sound pressure level [dB]",
        title="Reference floors (ISO 717-2 Table 4)")
ax1.legend()
cover.plot(ax=ax2)
plt.tight_layout()
plt.show()
```

</details>

### The form of Figure H.4

H.6.3 prints "an example of the form for the expression of results" and lets
the user copy it. `cover.report()` fills it: the manufacturer and product, the
client, the test room, who mounted the specimen, the date, the description of
facility and specimen, the type of reference floor, the mass per unit area,
the curing time, the air temperature and humidity in the source room and the
receiving room volume; the one-third-octave table of $L_\mathrm{n,0}$ and
$\Delta L$ beside the $\Delta L$ diagram with the frequency range of the
ISO 717-2 rating dashed, as key 1 of the form marks it; and the rating, with
the two floor ratings H.5 i) asks for beside it. The product identification
and the curing time come from the `product` and `curing_time_h` fields of
`ReportMetadata`.

```python
from phonometry import ReportMetadata

cover.report("covering.pdf", metadata=ReportMetadata(
    manufacturer="Example floorings", product="Resilient vinyl, 4 mm",
    mass_per_area=2.6, curing_time_h=0.0, source_temperature_c=21.2,
    source_relative_humidity_percent=48.0, receiving_volume=58.0))
```

The form also asks for $C_\mathrm{I,r,50\text{-}2500}$, a term of the
reference floor with the covering from 50 Hz, which the reference floors of
ISO 717-2:2020 Table 4 cannot give: they start at 100 Hz (see the
[errata registry](https://docs.jmrp.io/phonometry/reference/errata/)). The sheet says so where the number would
go.

[![ISO 10140-1 Figure H.4 example report: the form's header with manufacturer, product, reference floor type, mass per unit area, curing time and the climate of the source room, the one-third-octave table of Ln,0 and delta L beside the delta L diagram with the ISO 717-2 rating range dashed, the boxed delta Lw = 15 dB and CI,delta, the two floor ratings and a PASS verdict](https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/reports/iso10140_1_floor_covering_example.webp)](https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/reports/iso10140_1_floor_covering_example.pdf)

*The form of Figure H.4 (`LabFloorCoveringImprovementResult.report`), filled
with the floor and the covering of ISO 717-2:2020 Annex C: $\Delta L_\mathrm{w}
= 15$ dB, as Table C.2 prints it.*

## Joints: the sound reduction index per metre (Annex J)

A joint is a line, not an area: a slit with or without a filler, a foam or
sealing tape between two elements, the gasket on the rebate of a door or a
window. Annex J measures what it lets through. The joint is mounted in an
element that insulates far better than it does, the level difference is
measured to ISO 10140-2, and the result is normalized to a **metre** of joint
rather than to a square metre of element,

$$
R_\mathrm{s} = L_1 - L_2 + 10 \lg \frac{S_\mathrm{n} l}{A l_\mathrm{n}}
$$

(Formula (J.1)), with the joint length $l$, the equivalent absorption area $A$
of the receiving room, $S_\mathrm{n} = 1$ m² and $l_\mathrm{n} = 1$ m. A joint
twice as long lets twice the power through and lowers the level difference by
3 dB; the term in $l$ gives the 3 dB back, which leaves a number that does not
depend on how much of the joint the laboratory could fit in its opening.

```python
# One band: 95 dB in the source room, 48.6 dB in the receiving room, whose
# absorption area is 12.4 m2, with 5.4 m of rebate seal in the opening.
r = building.joint_sound_reduction_index([95.0], [48.6], [12.4],
                                         joint_length_m=5.4)
print(np.round(r, 1))                          # [42.8]
```

### The element around the joint is part of every measurement (J.1)

Whatever the joint lets through, the element it sits in lets something
through too, and a good seal can come close to it. So J.1 asks for the
**maximum** of the arrangement, $R_\mathrm{s,max}$: the same Formula (J.1)
with the joint sealed on both sides, "e.g. with elastic sealant". Unless the
maximum lies at least 10 dB above the measured index $R_\mathrm{s}'$, the
result is corrected by the rules of ISO 10140-2:2021 A.3, band by band, with
$d = R_\mathrm{s,max} - R_\mathrm{s}'$:

| Margin $d$ | $R_\mathrm{s}$ |
| :--- | :--- |
| 10 dB or more | $R_\mathrm{s}'$, no correction |
| 6 dB to 10 dB | $-10 \lg(10^{-R_\mathrm{s}'/10} - 10^{-R_\mathrm{s,max}/10})$, Formula (J.2) |
| under 6 dB | $R_\mathrm{s}' + 1{,}3$ dB, a minimum value |
| under 3 dB | $\geq R_\mathrm{s,max}$, in brackets |

The 1,3 dB is what Formula (J.2) gives at 6 dB, which is how A.3 puts it. A.3
itself stops correcting a sound reduction index at 15 dB and an
element-normalized level difference at 10 dB; Annex J writes the 10 dB, which
fits an index normalized to a reference length rather than to the area of
the opening, and the 10 dB is what the library applies. The
last row is exact rather than cautious: the arrangement passes the power of
the maximum alone, and the power of the joint on top of it when the joint is
open, so a measured index within 3 dB of the maximum means the joint passes
less than the element does, and its own index is above $R_\mathrm{s,max}$.
J.1 allows that lower limit ("may be set"); `limit_at_maximum=False` gives
those bands the 1,3 dB instead.

A rebate seal on a door, measured against its arrangement:

```python
freqs = [100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250,
         1600, 2000, 2500, 3150, 4000, 5000]
r_max = np.array([40.2, 42.8, 45.1, 48.6, 51.9, 54.3, 56.8, 58.9, 60.7, 62.4,
                  63.8, 65.1, 66.2, 67.0, 67.6, 68.1, 68.5, 69.0])
r_seal = np.array([33.4, 35.1, 37.9, 40.6, 43.0, 45.2, 46.1, 46.8, 47.0, 46.2,
                   45.1, 46.9, 49.8, 52.6, 55.4, 58.9, 63.1, 66.2])
seal = building.lab_joint_insulation(r_seal, r_max, freqs, joint_length_m=5.4)
print(seal.regime[-4:])
# ('uncorrected', 'corrected', 'limit', 'maximum')
print(np.round(seal.r_s_db[-4:], 1))           # [55.4 59.5 64.4 69. ]
```

The single numbers are those of ISO 717-1 on the corrected index, and the form
of Figure J.7 asks for the enlarged-range terms to 5 000 Hz as well:

```python
rating = seal.rating
print(rating.rating, rating.c, rating.ctr)               # 49 -1 -4
print(seal.c_100_5000_db, seal.ctr_100_5000_db)           # 0 -4
print(seal.max_rating.rating)                             # 61
```

Where a band is above $R_\mathrm{s,max} - 3$ dB, it says only that the joint
is better than the arrangement can show. J.1 rates the curve a second time
with an infinitely high index in those **indicative bands**, which then add no
unfavourable deviation and no energy, and if the two ratings differ by more
than 1 dB the single numbers go in brackets too. Here the only indicative band
is 5 000 Hz, outside the rating range, so nothing moves:

```python
print(seal.open_band_rating.open_frequencies_hz, seal.bracketed)  # (5000.0,) False
```

`seal.octave_bands()` averages the transmitted power of the three thirds of
each octave, the octave index Figure J.9 plots.

### The test element and the gap width (J.2)

J.2.1 asks for a joint longer than 1 m and no wider than 50 mm, and J.2.2 for
at least 5,0 m of a gap between the parts of a window or door, which may be
the sum of several gaps. The gap width $b$ is read at four positions or more,
evenly spread along the seal, and the readings "shall not deviate by more than
0,3 mm, otherwise readjust the mounting"; their average is the gap width.

```python
check = building.check_joint_test_element(5.4, 5.0, window_or_door_gap=True)
print(check.passes)                            # True
gap = building.check_gap_width([5.1, 4.9, 5.0, 5.15, 4.95])
print(round(gap.gap_width_mm, 2), round(gap.spread_mm, 2), gap.passes)
# 5.02 0.25 True
```

The deviation is read between the readings, the largest minus the smallest:
the sentence could also mean each reading against the average, which would let
the readings spread twice as far, and the stricter reading is the one checked.
Both verdicts have no truth value of their own: read `.passes`.

### A variable slit (J.4 and J.5)

An openable window or door does not have one gap width, so J.4 repeats the test
at three: the nominal width $b_\mathrm{n}$ the manufacturer gives (5 mm when
it gives none), the minimum width $b_\mathrm{min}$ under the maximal pressure
(normally a force of 100 N per metre of seal), and $b_\mathrm{n} + 3$ mm. The
report then gives every single number as a function of the gap width with the
nominal width marked (J.5.2 i)), and the results at $b_\mathrm{n}$ and
$b_\mathrm{n} + 3$ are the ones products are compared by (J.5.2 h)).

```python
loss = {3.0: -2.5, 4.0: -1.2, 5.0: 0.0, 6.0: 2.5, 8.0: 8.0, 10.0: 12.5,
        12.0: 13.0}                            # dB lost against 5 mm, mid band
slope = np.linspace(0.6, 1.4, 18)              # and more at high frequency
results = [building.lab_joint_insulation(
               np.minimum(r_seal - db * slope, r_max - 0.5), r_max, freqs)
           for db in loss.values()]
series = building.joint_gap_series(list(loss), results, minimum_gap_mm=3.0)
print(series.r_s_w_ctr_db)        # [48. 47. 45. 43. 38. 33. 33.]
print(series.at_gap(7.0), series.working_range_mm)        # 40.5 (5.0, 8.0)
```

`at_gap` reads the straight line between the two measured widths either side,
as Figure J.8 draws "lines plotted through measurement results", and never
extrapolates. Where J.5.2 h) lets "a gap range other than 3 mm" apply, it reads
the single numbers at that width as well; `working_range_mm` and the figure
keep the 3 mm that J.4 c) measures at. `series.plot_octave_bands()` draws
Figure J.9: the octave index at every gap width, under the closed and sealed
element ($b = 0$) as $R_\mathrm{s,max}$, which J.5.1 says the figure also
gives.

`joint_gap_series` collects any set of widths; whether the three of J.4 are
among them is a verdict of its own. J.4 gives no tolerance, so a width within
the 0,3 mm that J.2.2 lets the readings of a gap width spread over counts as the
width asked for, and a series that does not name $b_\mathrm{min}$ fails J.4 b),
since nothing then shows which width it was.

```python
widths = building.check_joint_gap_series(series)
print(widths.nominal_measured, widths.minimum_measured,
      widths.working_range_measured, widths.passes)     # True True True True
```

<picture><source media="(prefers-color-scheme: dark)" srcset="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/joint_insulation_dark.svg"><img src="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/joint_insulation.svg" alt="Two panels for an EPDM rebate seal on a door. Left: over 18 one-third-octave bands from 100 Hz to 5000 Hz, the maximum of the arrangement rising from 40 dB to 69 dB, the measured index of the seal from 33 dB to 66 dB with a dip near 1000 Hz, the corrected index just above it, and the shifted ISO 717-1 reference curve over 100 Hz to 3150 Hz; the 4000 Hz and 5000 Hz bands are marked as minimum values; the title reads R s w (C; C tr) equals 49 (minus 1; minus 4) dB. Right: the traffic single number R s A tr against the gap width from 3 mm to 12 mm, falling from 48 dB at 3 mm through 45 dB at the nominal 5 mm to 38 dB at 8 mm and 33 dB from 10 mm, with the working range from 5 mm to 8 mm shaded and the minimum width of 3 mm marked" width="100%"></picture>

*Left, the seal at its nominal gap: the measured index, the maximum of the
arrangement above it, and the corrected index, whose two top bands are minimum
values because the seal comes within 6 dB and then within 3 dB of what the
arrangement can show. Right, the same seal at seven gap widths: 7 dB of
$R_\mathrm{s,Atr}$ are lost across the 3 mm working range from the nominal
width.*

<details>
<summary>Show the code for this figure</summary>

```python
import matplotlib.pyplot as plt
import numpy as np
from phonometry import building

freqs = [100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250,
         1600, 2000, 2500, 3150, 4000, 5000]
r_max = np.array([40.2, 42.8, 45.1, 48.6, 51.9, 54.3, 56.8, 58.9, 60.7, 62.4,
                  63.8, 65.1, 66.2, 67.0, 67.6, 68.1, 68.5, 69.0])
r_seal = np.array([33.4, 35.1, 37.9, 40.6, 43.0, 45.2, 46.1, 46.8, 47.0, 46.2,
                   45.1, 46.9, 49.8, 52.6, 55.4, 58.9, 63.1, 66.2])
seal = building.lab_joint_insulation(r_seal, r_max, freqs, joint_length_m=5.4)
loss = {3.0: -2.5, 4.0: -1.2, 5.0: 0.0, 6.0: 2.5, 8.0: 8.0, 10.0: 12.5,
        12.0: 13.0}
slope = np.linspace(0.6, 1.4, 18)
results = [building.lab_joint_insulation(
               np.minimum(r_seal - db * slope, r_max - 0.5), r_max, freqs)
           for db in loss.values()]
series = building.joint_gap_series(list(loss), results, minimum_gap_mm=3.0)

fig, (ax1, ax2) = plt.subplots(1, 2, figsize=(13, 5.6))
seal.plot(ax=ax1)
series.plot(ax=ax2)
plt.tight_layout()
plt.show()
```

</details>

### The form of Figure J.7

J.5.1 prints a sample form for the result and J.5.2 b) asks the report for "a
data sheet with a diagram which shows the sound insulation of joints as a
function of the frequency". `seal.report()` writes it: the header of the form
(client, specimen, date, test length, separation wall, test noise, room
volumes, the maximum joint sound reduction index, mounting, and the climate of
both rooms), the table of $R_\mathrm{s}$ from 100 Hz to 5 000 Hz beside its
diagram over the printed 30 dB to 80 dB, with `≥` before a minimum value and
brackets round one set to the maximum, and the evaluation $R_\mathrm{s,w}$
($C$; $C_\mathrm{tr}$), $C_{100\text{-}5000}$ and
$C_\mathrm{tr,100\text{-}5000}$. When J.1 puts the single numbers in brackets,
every one of them is, and a note gives each of them rated with the indicative
bands open, so the one that moved is there to see. The separation wall and the
test noise come from the `separating_element` and `test_signal` fields of
`ReportMetadata`; the climate comes from the per-room fields when they are
given.

```python
seal.report("joint.pdf", metadata=ReportMetadata(
    client="Example client", separating_element="Lead-lined filler wall",
    test_signal="Pink noise", source_volume=53.0, receiving_volume=51.0))
```

[![ISO 10140-1 Figure J.7 example report: the form's header with the test length, separation wall, test noise and the maximum joint sound reduction index, the one-third-octave table of Rs from 100 Hz to 5000 Hz beside its diagram with the two top bands as minimum values, the boxed Rs,w (C; Ctr) with the enlarged-range terms and a PASS verdict](https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/reports/iso10140_1_joint_example.webp)](https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/reports/iso10140_1_joint_example.pdf)

*The form of Figure J.7 (`LabJointInsulationResult.report`), Rs,w (C; Ctr).*

## Rain on a roof (Annex K)

Rain is impact sound. It is measured as the **sound intensity level**
$L_I$ that the roof, roof window or rooflight radiates into the room below:
sound power per unit area, re $10^{-12}$ W/m² (K.1). Per unit area, because on
a large roof only part of the surface is wet, and the power grows with the
area the rain actually strikes.

### The rain

Natural rain is classed by rate, drop size and fall velocity (Table K.1, after
IEC 60721-2-2:1988): moderate up to 4 mm/h, intense up to 15 mm/h, heavy up to
40 mm/h and cloudburst above 100 mm/h, published as
`building.RAINFALL_CLASSIFICATION`. The laboratory reproduces two of them at
their upper limits, "since larger drops produce most of the sound generated"
(ISO 10140-5:2021 H.1), with a tank whose perforated base drops water from a
fixed height (Tables H.1 and H.2, `building.ARTIFICIAL_RAIN`):

| Artificial rain | Rainfall rate | Volume median drop diameter | Fall velocity | Holes and fall height |
| :--- | :--- | :--- | :--- | :--- |
| Intense (optional) | 15 mm/h | 2,0 mm | 4,0 m/s | 0,3 mm to 0,5 mm, about 25 per m², about 1 m |
| Heavy (mandatory) | 40 mm/h | 5,0 mm | 7,0 m/s | 1 mm, about 60 per m², about 3,5 m |

Heavy rain is the one products are compared under (K.4.1). The generator is
checked by its rate, which "shall be within ±2 mm/h" of the table; for a
generator that is not the tank of Table H.2, half of the drops should also lie
within ±0,5 mm of the median diameter and within ±1 m/s of the fall velocity.
The rate is measured by collecting the water, one litre per square metre being
one millimetre:

```python
rate = building.rainfall_rate(3.1, 0.08, 3600.0)     # litres, m², s
print(rate)                                          # 38.75 mm/h
check = building.verify_rain_generator(rate, rain_type="heavy")
print(check.passes, check.rate_deviation_mm_h)       # True -1.25
```

### The level

With the rain falling steadily for at least 5 min, the room-averaged sound
pressure level $L_\mathrm{pr}$ and the reverberation time $T$ of the test room
are measured to ISO 10140-4 and turned into the intensity level

$$
L_I = L_\mathrm{pr} - 10 \log_{10}\frac{T}{T_0} + 10 \log_{10}\frac{V}{V_0}
- 14 - 10 \log_{10}\frac{S_\mathrm{e}}{S_0}
$$

(Formula (K.1), $T_0 = 1$ s, $V_0 = 1$ m³, $S_0 = 1$ m²). The constant is the
diffuse-field sound power of a room with the Sabine area $A = 0.16\,V/T$,
$10 \log_{10}(0.16/4) \approx -14$ dB, and $S_\mathrm{e}$ is the area the rain
excites: the whole specimen for a roof window or rooflight of about
1,25 m × 1,5 m, and three times the perforated area of the tank for a large
roof of 10 m² to 20 m², which is rained on from three positions whose levels
are added energetically (K.4.2). The 18 bands from 100 Hz to 5000 Hz combine
into the A-weighted level,
$L_{I\mathrm{A}} = 10 \log_{10} \sum_j 10^{0.1(L_{Ij} + C_j)}$
(Formula (K.2)), whose 18 corrections $C_j$ of Table K.2 are the A-weighting
of IEC 61672-1:2013, the [frequency weighting](https://docs.jmrp.io/phonometry/signals/levels/weighting/)
of the library, at the exact midband frequencies of the bands, rounded to
0,1 dB (`building.RAINFALL_A_WEIGHTING`).
K.4.3 allows the intensity to be measured directly with a probe over a surface
$S_\mathrm{m}$ instead,
$L_I = L_{I\mathrm{m}} + 10 \log_{10}(S_\mathrm{m}/S_\mathrm{e})$
(Formula (K.4), `rainfall_sound_from_intensity`).

### Normalized to the reference pane

Two laboratories with the same tank still disagree, because their rain and
their mountings differ. K.6 therefore measures a **reference specimen** first:
a single 6 mm glass pane of 1,25 m × 1,5 m, mounted as a window pane and
centred under heavy rain (ISO 10140-5:2021 Annex I). Its structural
reverberation time $T_\mathrm{s}$ gives its loss factor,
$\eta = 2.2/(f T_\mathrm{s})$ (Formula (I.1)); its level is brought to the
reference loss factor of Table I.1,
$L_{I,\mathrm{m,ref}} = L_{I,\mathrm{ref}} + 10 \log_{10}(\eta/\eta_\mathrm{ref})$
(Formula (I.2)), and the difference from the reference level of the same table
is the laboratory's correction,
$\Delta L_{I\mathrm{c}} = L_{I,\mathrm{m,ref}} - L_{I\mathrm{c,ref}}$
(Formula (I.3)). Every specimen is then reported normalized,
$L_{I\mathrm{norm}} = L_I - \Delta L_{I\mathrm{c}}$ (Formula (K.5)).

```python
freqs = [100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250,
         1600, 2000, 2500, 3150, 4000, 5000]
# The reference pane, mounted a little more lossily than Table I.1 assumes.
l_i_ref = np.array([46.2, 45.8, 46.9, 46.5, 47.8, 47.2, 47.9, 48.1, 47.6,
                    46.8, 44.9, 43.1, 43.8, 46.9, 51.6, 50.9, 46.8, 44.6])
t_s = np.array([0.176, 0.177, 0.138, 0.139, 0.140, 0.111, 0.111, 0.088,
                0.088, 0.070, 0.070, 0.071, 0.055, 0.056, 0.044, 0.044,
                0.035, 0.035])
correction = building.rainfall_reference_correction(l_i_ref, t_s)

# A polycarbonate rooflight of 1.25 m x 1.5 m under heavy rain, 62 m3 room.
l_pr = np.array([48.2, 51.0, 53.1, 55.4, 57.0, 58.3, 59.1, 59.8, 60.2, 60.4,
                 60.1, 59.4, 58.6, 57.5, 56.2, 54.4, 52.3, 49.8])
t = np.array([1.9, 1.8, 1.7, 1.6, 1.5, 1.45, 1.4, 1.35, 1.3, 1.25, 1.2, 1.15,
              1.1, 1.05, 1.0, 0.95, 0.9, 0.85])
rain = building.rainfall_sound(l_pr, t, freqs, volume_m3=62.0,
                               excited_area_m2=1.875,
                               reference_correction=correction)
print(round(rain.l_ia_db, 1), round(rain.l_ia_norm_db, 1))     # 69.3 67.5
print(rain.octave_bands()[0])       # [ 125.  250.  500. 1000. 2000. 4000.]
```

K.5 e) asks for $L_I$, $L_{I\mathrm{norm}}$, $L_{I\mathrm{A}}$ and
$L_{I\mathrm{A,norm}}$ to 0,1 dB with the rainfall rate beside them. The sound
power the whole specimen radiates follows from the NOTE to Formula (K.2),
$L_W = L_I + 10 \log_{10}(S/S_0)$, as `rain.sound_power_levels(area_m2)`.

<picture><source media="(prefers-color-scheme: dark)" srcset="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/rainfall_sound_dark.svg"><img src="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/rainfall_sound.svg" alt="Two panels over 18 one-third-octave bands from 100 Hz to 5000 Hz. Left: the reference pane's level corrected to the reference loss factor, between 44 and 53 dB, above the Table I.1 reference level, which runs from 45 dB through a dip of 42 dB at 1250 Hz to a peak of 51 dB at 2500 Hz and back to 44 dB; the gap between them, shaded, is the laboratory correction of about 1.2 to 2.2 dB. Right: the sound intensity level of a rooflight under heavy rain rising from 47 dB at 100 Hz to about 61 dB at 800 Hz and falling to 52 dB at 5000 Hz, with the normalized level about 2 dB below it; the title reads L I A equals 69.3 dB and L I A norm equals 67.5 dB" width="100%"></picture>

*Left, the laboratory's reference pane, corrected to the reference loss
factor, against the reference level of Table I.1: the shaded gap is the
correction every later specimen is normalized by. Both curves peak at 2500 Hz,
just above the coincidence frequency of a 6 mm pane. Right, a rooflight under
heavy rain: the intensity level as measured and normalized, and its A-weighted
totals.*

<details>
<summary>Show the code for this figure</summary>

```python
import matplotlib.pyplot as plt
import numpy as np
from phonometry import building

freqs = [100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250,
         1600, 2000, 2500, 3150, 4000, 5000]
l_i_ref = np.array([46.2, 45.8, 46.9, 46.5, 47.8, 47.2, 47.9, 48.1, 47.6,
                    46.8, 44.9, 43.1, 43.8, 46.9, 51.6, 50.9, 46.8, 44.6])
t_s = np.array([0.176, 0.177, 0.138, 0.139, 0.140, 0.111, 0.111, 0.088,
                0.088, 0.070, 0.070, 0.071, 0.055, 0.056, 0.044, 0.044,
                0.035, 0.035])
correction = building.rainfall_reference_correction(l_i_ref, t_s)
l_pr = np.array([48.2, 51.0, 53.1, 55.4, 57.0, 58.3, 59.1, 59.8, 60.2, 60.4,
                 60.1, 59.4, 58.6, 57.5, 56.2, 54.4, 52.3, 49.8])
t = np.array([1.9, 1.8, 1.7, 1.6, 1.5, 1.45, 1.4, 1.35, 1.3, 1.25, 1.2, 1.15,
              1.1, 1.05, 1.0, 0.95, 0.9, 0.85])
rain = building.rainfall_sound(l_pr, t, freqs, volume_m3=62.0,
                               excited_area_m2=1.875,
                               reference_correction=correction)

fig, (ax1, ax2) = plt.subplots(1, 2, figsize=(13, 5.6))
correction.plot(ax=ax1)
rain.plot(ax=ax2)
plt.tight_layout()
plt.show()
```

</details>

## How the measurement goes

<picture><source media="(prefers-color-scheme: dark)" srcset="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/diagram_lab_application_rules_dark.svg"><img src="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/diagram_lab_application_rules.svg" alt="Four sections through the laboratory, one per annex of ISO 10140-1. A lining, Annex G: a basic element in the test opening between the source and receiving rooms with a lining on the receiving side; R without the lining and then with it, the improvement band by band; a heavy wall of about 350 kg/m² with its critical frequency near 125 Hz or a lightweight wall of about 70 kg/m² near 500 Hz; no rigid fixing at the edges and the curing rule of G.4. A floor covering, Annex H: a tapping machine on one of three category I pieces on the reference floor and a microphone in the receiving room below; the improvement as L_n0 minus L_n at the same positions; pieces of 650 mm by 350 mm or more with the hammers 100 mm from their edges, large specimens wall to wall or of 10 m² with a shorter side of 2.3 m, four tapping positions on the heavy floor and six on a light one. A joint, Annex J: a high R element with a slit between the source level L_1 and the receiving level L_2, and in elevation a joint longer than 1 m and no wider than 50 mm read at four places; R_s per metre from Formula (J.1), the sealed maximum and its 10 dB margin, gaps of windows and doors 5.0 m long, and the three widths of J.4. Rain on a roof, Annex K: a sloping specimen over the test room under a rain tank; heavy rain held steady for at least 5 min before reading, a slope of at least 5 degrees for roofs and rooflights and 30 degrees for roof windows, an opening of 10 m² to 20 m² with an edge of 2.3 m, and one tank position on a small element or three on one of 10 m² to 20 m², the drops landing slightly off-centre" width="100%"></picture>

**A lining.** Build the basic element in the test opening (the heavy wall, the
heavy floor or the lightweight wall of ISO 10140-5 Annex B, or the wall of
interest), let it cure, and measure $R_\mathrm{without}$ to ISO 10140-2. Fix
the lining as it would be fixed in practice, with no stiff connection to the
laboratory's flanking elements (G.3), let it reach its final condition, and
measure $R_\mathrm{with}$ within the G.4 time lag. Report both curves, the
improvement, the single numbers with the element index, and the element's mass
and construction (G.5).

**A floor covering.** Measure $L_\mathrm{n0}$ on the bare reference floor to
ISO 10140-3, lay the covering by category, and measure $L_\mathrm{n}$ at the
same tapping-machine positions. Report the category, the specimen, the
positions, the load, the floor temperature, $\Delta L$ with its weighted value
and adaptation term, and the two ratings of H.5 i).

**A joint.** Build the joint into an element that insulates far better than
it does, at least 1 m long and no wider than 50 mm (5,0 m for a gap between
the parts of a window or door), read the gap width at four positions or more,
and measure $L_1$, $L_2$ and the reverberation time to ISO 10140-2. Seal the
joint on both sides and measure the arrangement's maximum the same way. A
variable slit is measured again at its minimum width under load and at its
nominal width plus 3 mm. Report the maximum, the data sheet of Figure J.7 for
each gap width, the test element and the cross-section with its gap width, and
the single numbers against the gap width (J.5.2).

**Rain.** Install the specimen at its slope (at least 5° for roofs and
rooflights, 30° for roof windows) in an opening of 10 m² to 20 m², or a
roof window in a heavy filler construction; check the rain rate; rain on it
steadily for 5 min before measuring; measure $L_\mathrm{pr}$, $T$ and the
background, from one generator position or three; and normalize with the
laboratory's own reference pane. Report the rain type and rate, the generator
and its position, $L_I$ and $L_{I\mathrm{norm}}$ to 0,1 dB, and the A-weighted
totals (K.5).

## Verifying it

The printed tables and examples of the four annexes, and the tables behind
them, are conformance rows:

- The **reference curves, band by band**: the 63 values of ISO 717-1:2020
  Table E.1 and the 48 of ISO 717-2:2020 Table 4, against a reading of the
  page kept apart from the library, and the **single numbers under them**:
  the nine terms of Table E.1 under each of the three basic elements, integer
  and to one decimal place (54 numbers), and $L_\mathrm{n,r,0,w}$ with
  $C_{\mathrm{I,r,0}}$ under each of the three curves of Table 4, both forms
  (12 numbers), which the published curves reproduce through the ISO 717
  rating engine. The band values are needed as well as the single numbers,
  because a single number does not move with every band: a decibel mistyped at
  4 000 Hz of the heavy floor changes none of them.
- A **sloped improvement on every reference floor** and a **sloped lining on
  every standard element**, rated by a separate implementation of the printed
  clauses of ISO 717-1 and ISO 717-2: a flat spectrum gives the same number on
  every curve, and the same $\Delta(R_\mathrm{w} + C)$ as
  $\Delta(R_\mathrm{w} + C_\mathrm{tr})$, while a sloped one tells them
  apart. The direct differences of Formula (D.2) are checked on the same
  sloped lining. A second lining, with its mass-spring-mass resonance at
  100 Hz and a coincidence dip at 4 000 Hz, puts weight on the bands 50 Hz to
  80 Hz and 4 000 Hz to 5 000 Hz that set the enlarged ranges apart: rated
  the same way, it gives every two of the nine lining terms different numbers
  on at least one element, so no two of them could be swapped unseen.
- The **18 $C_j$ of Table K.2** against the A-weighting of IEC 61672-1 at the
  exact midband frequencies, rounded to 0,1 dB: all 18 agree. The same 18
  values, as printed, also carry a flat spectrum through Formula (K.2), so a
  mistyped $C_j$ in the published table would show in $L_{I\mathrm{A}}$.
- The **ISO 717-2 Annex C example**, carried end to end through the Annex H
  front end: $\Delta L_\mathrm{w} = 15$ dB as printed, and
  $C_{\mathrm{I}\Delta} = -9$ dB from the Table 4 floor, where the example's
  own chain gives −8 dB (see the [errata registry](https://docs.jmrp.io/phonometry/reference/errata/)).
- The **G.4 example**: measurements within 1 d that start 3 d after
  construction pass, and 2,9 d fails. The bound is inclusive on any input:
  2,1 d after 6,3 d passes as well, although 3 × 2,1 comes out a rounding
  error above 6,3 in binary arithmetic.
- **Tables K.1, H.1, H.2 and I.1** cell by cell as printed, and Formulas
  (I.1) to (I.3) on a pane at twice the reference loss factor of the printed
  Table I.1, which has to come out $10 \log_{10} 2$ dB in all 18 bands.
- The **H.1 tolerance** at its bounds, which it includes: 38 mm/h passes,
  also when it comes out of `rainfall_rate` as 3,8 L collected on 0,1 m² in
  one hour, a rounding error below 38. Then Formula (K.1) with every term away
  from zero, and closed forms of Formulas (D.4) and (K.4).

- **Annex J** at its printed numbers: the fixed 1,3 dB below a 6 dB margin is
  Formula (J.2) at 6 dB to the printed decimal, as ISO 10140-2:2021 A.3 says
  it corresponds, and the library applies exactly that just below it; the
  lower limit J.1 prints as its example, $R_\mathrm{s} \geq 50{,}4$ dB in brackets;
  and the typical flanking spectrum of ISO 10140-2:2021 Table A.1 carried
  through the joint front end, rated 59 ($-2$; $-7$) dB as printed. Then
  Formula (J.1) with every term away from zero, the bounds of J.2.1 and J.2.2
  at their printed values, each inclusive or exclusive as the text says, the
  three gap widths of J.4 with the 5 mm taken when the nominal width is
  unknown and the 3 mm above it, and the open-band rating checked by hand
  against ISO 717-1 Clauses 4.4 and 4.5.

The rain has no worked example in either standard, so Formulas (K.1) to (K.5)
are checked in closed form rather than against a printed result. Tables H.1
and I.1 were read on the pages of the 2021 edition and agree digit for digit
with the 2010 edition and its 2014 amendment, where they first appeared.

## Quick answers

### Is ΔRw the difference of the two measured Rw?

Only on a wall that is not a standard basic element, where it is
$\Delta R_\mathrm{w,direct}$. On a standard element the measured $\Delta R$ is
added to the element's reference curve and the two reference ratings are
subtracted, which removes the particular wall of the laboratory from the
number. In the example above the two differ by a decibel, 12 dB against 13 dB.

### Why is my covering 18 dB on concrete and 8 dB on timber?

Because the two ratings read the same $\Delta L$ against different reference
floors. The concrete reference curve is loudest at high frequency, where a
resilient covering works best; the timber curves are loudest below 400 Hz,
where it barely works. A $\Delta L_\mathrm{w}$ measured on concrete applies to
massive floors only (ISO 717-2:2020 5.4).

### Why is a band of my joint in brackets?

Because the joint came within 3 dB of what the arrangement can show there, so
the measurement says only that the joint is better than $R_\mathrm{s,max}$:
the band is reported as $(R_\mathrm{s} \geq R_\mathrm{s,max})$. A better
filler wall or a better seal on the sealed measurement raises the maximum and
turns the band into a number. If such bands also move the single numbers by
more than 1 dB, the single numbers go in brackets too (J.1).

### Do I need the reference pane to report rain noise?

The intensity level $L_I$ and $L_{I\mathrm{A}}$ are reported without it. The
normalized levels, which are what makes two laboratories comparable, need the
laboratory's own reference measurement (K.6, K.5 f)). No reference specimen is
defined for large roofs (ISO 10140-5:2021 I.3).

## References

- International Organization for Standardization. (2021). *Acoustics — Laboratory
  measurement of sound insulation of building elements — Part 1: Application
  rules for specific products* (ISO 10140-1:2021). Third edition.
  Annex G (linings: ΔR, the curing condition of G.4 and the report of G.5),
  Annex H (floor coverings: Formulae (H.1) to (H.3), the three categories of
  covering, the tapping-machine positions and the form of Figure H.4),
  Annex J (joints: Formulae (J.1) and (J.2), the test element of J.2, the gap
  widths of J.4 and the form of Figure J.7) and Annex K (rainfall sound:
  Formulae (K.1) to (K.5) and the 18 $C_j$ of Table K.2).
- International Organization for Standardization. (2021). *Acoustics — Laboratory
  measurement of sound insulation of building elements — Part 2: Measurement
  of airborne sound insulation* (ISO 10140-2:2021). Second edition. A.3, the
  correction for flanking through the filler wall that Annex J applies to a
  joint, and Table A.1, the typical flanking spectrum of a small test opening.
- International Organization for Standardization. (2021). *Acoustics — Laboratory
  measurement of sound insulation of building elements — Part 5: Requirements
  for test facilities and equipment* (ISO 10140-5:2021). Annexes B and C build
  the standard basic elements and the four reference floors and refer to
  ISO 717 for their curves; Annex H specifies the two artificial rains
  (Tables H.1 and H.2) and Annex I the reference glass pane (Table I.1,
  Formulae (I.1) to (I.3)). Annex F specifies the rubber ball of H.6.1.
- International Organization for Standardization. (2020). *Acoustics — Rating of
  sound insulation in buildings and of building elements — Part 1: Airborne
  sound insulation* (ISO 717-1:2020). Clauses 4.4 and 4.5 with Annex B rate a
  joint, $R_\mathrm{s,w}$ ($C$; $C_\mathrm{tr}$) with $C_{100\text{-}5000}$ and
  $C_\mathrm{tr,100\text{-}5000}$, also with its indicative bands taken as
  infinitely high; Annex D rates a lining on a standard basic element
  (Formulae (D.1) to (D.4)); Annex E prints the reference curves of the three
  elements, Table E.1, with every single number under them.
- International Organization for Standardization. (2020). *Acoustics — Rating of
  sound insulation in buildings and of building elements — Part 2: Impact
  sound insulation* (ISO 717-2:2020). Clauses 5 and 6 rate a floor covering on
  the heavyweight and on the lightweight reference floors; Table 4 prints the
  four reference curves; A.2.2 and A.2.3 give the adaptation terms
  $C_{\mathrm{I}\Delta}$ and $C_{\mathrm{I}\Delta,\mathrm{t}}$.

## Standards

ISO 10140-1:2021 Annex G: the sound reduction improvement index $\Delta R$ of
G.1, its octave values, the single numbers $\Delta R_\mathrm{w}$,
$\Delta(R_\mathrm{w} + C)$ and $\Delta(R_\mathrm{w} + C_\mathrm{tr})$ with every
enlarged-range term on the three standard basic elements (ISO 717-1:2020
Annex D, Formulae (D.1) to (D.4)), the direct differences of Formula (D.2), and
the curing condition of G.4. Annex H: $\Delta L$ of Formula (H.1), the octave
values of Formula (H.2), the weighted reductions $\Delta L_\mathrm{w}$ and
$\Delta L_\mathrm{t,n,w}$ with $C_{\mathrm{I}\Delta}$ and
$C_{\mathrm{I}\Delta,\mathrm{t}}$ on all four reference floors (ISO 717-2:2020
Clauses 5 and 6, A.2.2, A.2.3), the two ratings of H.5 i), the heavy/soft
improvement of Formula (H.3), and the form of Figure H.4 as a `.report()` PDF.
Annex J: the sound reduction index of joints per metre of Formula (J.1), the
correction for the test arrangement of Formula (J.2) with the rules of
ISO 10140-2:2021 A.3 (no correction from 10 dB, the fixed 1,3 dB below 6 dB,
the lower limit at $R_\mathrm{s,max}$ below 3 dB), the ISO 717-1 single
numbers with $C_{100\text{-}5000}$ and $C_\mathrm{tr,100\text{-}5000}$, the
rating with infinitely high indicative bands and the 1 dB bracket rule, the
length and width of the test element (J.2.1, J.2.2), the gap-width readings
(J.2.2), the gap widths of a variable slit with the check that the three of
J.4 were measured and the single numbers against the gap width (J.4,
J.5.2 h) and i), Figures J.8 and J.9), and the form of
Figure J.7 as a `.report()` PDF. Annex K: Formulae (K.1) to (K.5), the 18 $C_j$ of
Table K.2, three generator positions, the background correction, the rain
classes of Table K.1, the artificial rains and tolerances of ISO 10140-5:2021
Tables H.1 and H.2 with the rate check of H.2.3, and the reference-pane
correction of its Annex I (Table I.1, Formulae (I.1) to (I.3)). The reference
curves of ISO 717-1:2020 Table E.1 and ISO 717-2:2020 Table 4 are published
read-only tables.

**Not covered.** The mounting, specimen and procedure requirements of the four annexes are
documented above and checked only where G.4, J.2 and ISO 10140-5 H.1 put a
verdict on them: nothing checks the covering category, the specimen sizes, the
number and placement of tapping-machine positions, the load, the floor
temperature, the slope of a roof or the 5 min of steady rain, and for a joint
nothing checks the uniform cross-section, the shape of Figure J.1, that the
gap readings are evenly spread, the force of 100 N/m behind the minimum gap
width or the time a sealing band takes to expand. A working range other than
the 3 mm of J.4, which J.5.2 h) allows for comparisons, is read with `at_gap`
but not drawn. The wooden mock-up of H.6.2
has no reference curve of its own. The form of Figure H.4 asks for a
$C_{\mathrm{I,r,50\text{–}2500}}$ that the reference floor cannot give, since
Table 4 starts at 100 Hz (recorded in the [errata registry](https://docs.jmrp.io/phonometry/reference/errata/));
the sheet says so in its place, and the bare floor's own enlarged-range term is
available from `weighted_impact_rating_extended`. The measurements that feed
these annexes, $R$, $L_\mathrm{n}$ and the reverberation times, are those of
[Laboratory Insulation Measurement](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-lab/), and the other annexes
of ISO 10140-1 are mounting rules for that $R$ and $L_\mathrm{n}$ (walls,
doors, windows, glazing, small technical elements, floors, shutters).

## See also

- [Laboratory Insulation Measurement](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-lab/):
  the $R$ and $L_\mathrm{n}$ of ISO 10140-2 and -3 that every annex here starts
  from.
- [Insulation Ratings (ISO 717)](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-ratings/):
  the reference-curve engine that rates both reference curves.
- [Heavy and Soft Impact Sources](https://docs.jmrp.io/phonometry/buildings/insulation/heavy-impact-sources/):
  the rubber ball of H.6.1 and its single number.
- [Floor-Covering Impact Improvement (ISO 16251-1)](https://docs.jmrp.io/phonometry/buildings/design/impact-improvement/):
  the small-mock-up alternative for soft coverings.
- [Predicting Resilient-Layer Performance](https://docs.jmrp.io/phonometry/buildings/design/resilient-layers/):
  the ISO 12354 prediction of a lining's improvement from its resonance, and
  its transfer from the laboratory to the field.
- [Sound Insulation by Intensity (ISO 15186)](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-intensity/):
  the intensity method K.4.3 allows for rain.
- API reference:
  [`building.measurement.lab_improvement`](https://docs.jmrp.io/phonometry/reference/api/building/lab-improvement/),
  [`building.measurement.joint_insulation`](https://docs.jmrp.io/phonometry/reference/api/building/joint-insulation/),
  [`building.measurement.rainfall_sound`](https://docs.jmrp.io/phonometry/reference/api/building/rainfall-sound/)
  and [`building.measurement.ratings`](https://docs.jmrp.io/phonometry/reference/api/building/ratings/).